CyberPower UPS OLS Tower 3000VA/2400W 7AH*6,LCD (OLS3000EC-AS)
Specification
General
Phase | Single Phase |
Form Factor | Tower |
UPS Topology | Online Double Conversion |
Energy Saving Technology | Online ECO Mode Efficiency > 95% |
Active PFC Compatibility | Yes |
Input
Generator Compatibility | Yes |
Nominal Input Voltage ( Vac ) | 220 ± 25% |
Input Voltage Range ( Vac ) | 110 ~ 300 |
Input Frequency ( Hz ) | 50 ± 10, 60 ± 10 |
Input Frequency Detection | Auto-sensing |
Rated Input Current ( A ) | 13.04 |
Input Power Factor | 0.98 |
Input Connector Type | IEC C20 |
Detachable Power Cord Plug Type | NEMA 5-15P x 1 |
Power Cord Length (ft.) | 5 |
Power Cord Length (m.) | 1.5 |
Output
Capacity (VA) | 3000 |
Capacity (Watts) | 2400 |
On Battery Waveform | Pure Sine Wave |
On Battery Voltage(s) (Vac) | 208 ± 1% 220 ± 1% 230 ± 1% 240 ± 1% |
Output Voltage Setting | Configurable |
On Battery Frequency (Hz) | 50 ± 0.5%, 60 ± 0.5% |
Output Frequency Setting | Configurable |
Power Factor | 0.8 |
ECO Mode Voltage Tolerance | ± 15 % |
Overload Protection | Internal Current Limiting, Circuit Breaker, Fuse |
Overload Protection (Line Mode) | 110~120% Load for 1 min, >120% Load Immediately |
Overload Protection (Battery Mode) | 110~120% Load for 10 sec, >120% Load Immediately |
Overload Protection (Bypass Mode) | >130% Load Immediately |
Crest Factor | 3 : 1 |
Harmonic Distortion (Linear Load) | THD<3% |
Harmonic Distortion (Non-linear Load) | THD<5% |
Internal Bypass | Automatic Bypass, Manual Bypass |
Outlet(s) – Total | 7 |
Outlet Type | IEC C13 x 2
AS x 4 Hardwire Terminal Block x 1 |
Outlet(s) – Battery & Surge Protected | 6 |
Typical Transfer Time (ms) | 0 |
Battery
Runtime at Half Load ( min ) | 10 |
Runtime at Full Load ( min ) | 4 |
Typical Recharge Time ( Hours ) | 4 |
Maximum Charging Current ( A ) | 1 |
Start On Battery | Yes |
Smart Battery Management (SBM) | Yes |
User-replaceable | No |
Battery Type | Sealed Lead-acid |
Warranty
- 2 years warranty, onsite service
รีวิว
ยังไม่มีบทวิจารณ์